Fuse selection for a photovoltaic string is a structured exercise. Working through the following checks in order helps avoid the common mistake of choosing a fuse on current rating alone.
1. Confirm the DC Voltage Rating
The fuse voltage rating must meet the maximum system voltage of the array, including the fully charged open-circuit condition. A rating based only on nominal voltage can be exceeded in practice.
2. Check Current and Operating Conditions
Account for the module's short-circuit current, expected irradiance and any continuous operating conditions. The fuse should carry normal current without nuisance operation while providing protection under fault conditions.
3. Evaluate Reverse-Current Conditions
In a parallel string arrangement, a failed string can be fed by the others. The fuse must be able to interrupt this reverse current, which is a defining requirement for gPV fuse links.
4. Review Breaking Capacity and Installation
Confirm the DC breaking capacity at the system voltage and check the mechanical fit — fuse base compatibility, terminal type and clearances. Verify every rating against the current technical documentation for the exact model before specifying.